The Crowcon Hydra Addressable Gas Detection System is designed to monitor toxic and/or flammable gas hazards, particularly in car park applications.
(click image to enlarge)
Quick Overview

    Overview

    Hydra is available in two versions, allowing connection of a maximum of 32 or 256 detectors to a single panel via addressable RS-485 loops.

    Features include:

    • Able to control up to 32, 64 or 256 remote outputs, all of which are programmable
    • Built-in relays can be used to indicate the system status remotely or provide control of auxiliary equipment
    • Modbus RTU output for connection to Building Management Systems (BMS)
    • Event log functions
    • Optional battery back up
Interested in this item or want more information?
Call Mon. through Fri. 8:00 AM - 5:00 PM PST
Phone: 714-573-4083
Email: sales@48ws.com

Can't find what you want? Give us a call and we can help you find it.
Details

Specifications

  Hydra32 Hydra256 Hydra+
Size 486W x 288H x 148D mm (19.1x11.3x5.8 ins)  430W x 405H x 140D mm (16.9x16x5.5 ins)  100W x 180H x 65D mm (3.9x7x2.5 ins)
Weight 3.8Kg (8.4lbs) 7.9Kg (17.4lbs) 0.4kg (0.9lbs)
Enclosure material ABS Painted steel Painted alloy
Ingress protection IP65 N/A IP55
Operating temperature 0 to +55°C (32 to 131°F) -10 to +55°C (14 to 131°F)
Storage temperature -20 to +60°C (-4 to 140°F)
Humidity 15-85%RH non-condensing 20-90%RH non-condensing (RH @40°C)
Battery back-up 2 x 12V 7Ah lead-acid batteries (optional) 2 x 12V 7Ah lead-acid batteries (optional) N/A
Inputs 1-32 addressable Hydra+ gas detectors (RS-485, maximum cable length 1Km typically) Up to 256 addressable Hydra+ gas detectors. Two RS-485 buses supplied (max. 128 detectors), two extra buses may be added N/A
Outputs 3 x alarm relays (alarm level 1,2,3)
1 x fault relay
All relays are single-pole changeover (SPCO) with contacts rated 1A 24Vdc.
3 x alarm relays (alarm level 1,2,3)
1 x fault relay
1 x power fail relay
1 x battery relay
1 x sounder relay
1 x test relaySPCO contacts rated 16A 230Vac
RS-485 Modbus
Addressable output modules One or two 16-way modules can be connected to provide up to 32 additional open-collector type outputs, or up to 32 SPCO relays when used with 8-way relay modules. One to four 16-way modules can be connected per RS-485 bus to provide up to 64 additional open-collector outputs, or up to 64 SPCO relays when used with 8-way relay modules. 256 outputs maximum N/A
  Relays can be energised/de-energised, latched/non-latched, time-delayed, pulsed. Contacts rated 16A 230Vac
Digital communications RS-485 Modbus communication to BMS/DCS/PLC systems. System configuration software and PC lead/converter supplied. RS-232 port for system configuration via a PC (software and lead supplied), or for Modbus communication to BMS/DCS/PLC systems. N/A
Event logging Up to 1000 alarm, power, fault, system events are stored in NVM. Up to 1000 alarm, power, fault, system events are stored in NVM and on SD card. N/A
Panel indication OLED text display, 96 x 64 pixels LED’s:
6 x red Alarm (alarm level 1,2,3)
2 x yellow Fault
2 x green TX/RX
Piezo sounder
Graphic LCD
LED’s:
6 x red Alarm (alarm level 1,2,3)
2 x yellow Fault
2 x yellow Over-range
2 x yellow Under-range
2 x green Power/battery
2 x yellow Inhibit/test
N/A
Gases and ranges     CO: 0-300ppm
NO2 : 0-20ppm LPG/Propane: 0-100% LEL
Sensor life     4 years typical
Approvals EMC: EN50270, EN61000-6-3: 2001 + A11 (2004), FCC CFR 47 Part 15, ICES-002 EMC: EN50270, EN61000-6-3: 2001 + A11 (2004) N/A